Neutral insulation resistance is measured to ensure no
shunt ground paths exist downstream of the sensor.
·
Pick up current is measured by primary injection at
the sensor.
·
Pick up current is tested at each pick up tap
setting.
·
Verify correct sensor polarities on residual
systems single main and double ended substations.
·
Verify correct sensor polarities on zero sequence
systems double ended substations.